logo

Standards Manage Your Business

We Manage Your Standards

ASTM

ASTM B779 : 12

Standard Specification for Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Steel-Reinforced (ACSR/TW)

Standard Details

1.1 This specification covers shaped wire compact concentric-lay-stranded aluminum conductor, steel-reinforced (ACSR/TW) and its component wires for use as overhead electrical conductors (Explanatory Note 1 and Note 2).

1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

Note 1ACSR/TW is designed to increase the aluminum area for a given diameter of conductor by the use of trapezoidally shaped wires (TW). The conductors consist of a central core of round steel wire(s) surrounded by two or more layers of trapezoidal aluminum 1350-H19 wires. Different strandings of the same size of conductor are identified by type, which is the approximate ratio of steel area to aluminum area expressed in percent (Table 1, Table 2 and Table 3). For the purpose of this specification, the sizes listed in Table 1 and Table 2 are tabulated on the basis of the finished conductor having an area or outside diameter equal to that of specific sizes of standard ACSR so as to facilitate conductor selection.
TABLE 1 Construction Requirements for Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Reinforced Size to Have Area Equal to ACSR, Class AA

ACSR/TW Conductor
Size

Size and Stranding of ACSR with Equal Area

Number of Aluminum Wires

Number of Layers

Steel Core Stranding

Mass per Unit Length,A
lb/1000 ft

Rated
Strength,
1000 lbB

Nominal
Outside
Diameter, in.

kcmil

Type

kcmil

Stranding

Number of Wires

Diameter,
in.

 336.4

 6

 336.4

18/1

14

2

1

0.1367

 365

 8.6

0.63

 477.0

13

 477.0

24/7

18

2

7

0.0940

 613

17.2

0.78

 477.0

16

 477.0

26/7

18

2

7

0.1053

 655

19.4

0.79

 556.5

13

 556.5

24/7

18

2

7

0.1015

 715

20.0

0.84

 556.5

16

 556.5

26/7

20

2

7

0.1138

 765

22.6

0.85

 636.0

 3

 636.0

36/1

27

3

1

0.1329

 646

13.5

0.85

 636.0

13

 636.0

24/7

18

2

7

0.1085

 816

22.9

0.89

 636.0

16

 636.0

26/7

20

2

7

0.1216

 874

25.4

0.91

 795.0

 7

 795.0

45/7

17

2

7

0.0886

 892

21.0

0.96

 795.0

10

 795.0

22/7

18

2

7

0.1108

 975

25.9

0.98

 795.0

13

 795.0

54/7

20

2

7

0.1213

1021

28.2

0.99

 795.0

16

 795.0

26/7

20

2

7

0.1360

1092

31.8

1.01

 954.0

 5

 954.0

42/7

30

3

7

0.0837

1029

23.7

1.05

 954.0

 7

 954.0

45/7

32

3

7

0.0971

1075

25.9

1.06

 954.0

13

 954.0

54/7

20

2

7

0.1329

1226

33.5

1.08

1033.5

 5

1033.5

42/7

30

3

7

0.0871

1115

25.7

1.09

1033.5

 7

1033.5

45/7

32

3

7

0.1010

1165

28.1

1.10

1033.5

13

1033.5

54/7

21

2

7

0.1363

1327

36.3

1.13

1113.0

 5

1113.0

42/7

30

3

7

0.0904

1201

27.5

1.13

1113.0

 7

1113.0

45/7

33

3

7

0.1049

1254

30.3

1.14

1113.0

13

1113.0

 54/19

38

3

19

0.0862

1429

39.1

1.19

1192.5

 5

1192.5

42/7

30

3

7

0.0936

1286

29.5

1.17

1192.5

 7

1192.5

45/7

33

3

7

0.1085

1343

32.4

1.18

1192.5

13

1192.5

 54/19

38

3

19

0.0892

1530

41.9

1.22

1272.0

 5

1272.0

42/7

30

3

7

0.0967

1372

31.4

1.20

1272.0

 7

1272.0

45/7

35

3

7

0.1121

1433

34.6

1.22

1272.0

13

1272.0

 54/19

39

3

19

0.0921

1632

44.1

1.26

1351.5

Status : Historical
Standard Type: Main
Document No: ASTM B779 : 12
Document Year: 2012
Pages: 6
  • Section Volume:
  • 02.03 Volume 02.03 Electrical Conductors
  • ICS:
  • 29.240.20 Power transmission and distribution lines

Life Cycle

Historical

Historical

Currently Viewing

Historical
ASTM B779 : 12

Historical

Historical

© Copyright 2024 BSB Edge Private Limited.